Windload Ratings for Panels Manufactured in all Metl-Span Plants
Fastening Pattern 10
Metl-Span's FM 4881 Windload Ratings for Panels Manufactured in all Metl-Span Plants-Fastening Pattern 10
Test results from this program and prior Approval programs sponsored by Metl-Span LLC indicate that 2 to 6 in. (50 to 150 mm) thick Metl-Span CF-Flute, CF-Mesa, CF-Light Mesa, CFI-Flute, CFI-Mesa, CFI-Light Mesa and CFI-Metl-Plank exterior wall panels produced with minimum 26 ga. [minimum 0.0170 in. (0.432 mm) base steel thickness] painted (optional) stainless, galvanized or Galvalume steel interior and exterior facers and an Approved foam system meet the Approval requirements of the Standard listed above as indicated in the tables below when installed as indicated below.
|
Manufacturer |
Wall Panels |
Thickness |
Width |
Max Height |
Hail Rating |
|
Metl-Span LLC |
Metl-Span CF-Flute, CF-Mesa,CF-Light |
2-6 in. (50 to 150 mm) |
42 in. (1065 mm) |
No Limit |
Class S (severe) |
|
Wall Panel Min Thickness |
Panel Securemet |
Wind Load Rating & Zone |
Max Support Steel Spacing |
Min Support Steel Thickness |
Min Support Steel Yield Stress |
|
4.0 in. (100 mm) |
FP10 |
Class +35/-49 |
15 ft 9 in. (4800 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +40/-56 |
14 ft 0 in. (4265 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +45/-63 |
12 ft 0 in. (3660 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +50/-70 |
11 ft 0 in. (3355 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +55/-77 |
10 ft 0 in. (3050 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +60/-84 |
9 ft 0 in. (2745 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +70/-98 |
8 ft 0 in. (2440 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +80/-112 |
7 ft 0 in. (2135 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
4.0 in. (100 mm) |
FP10 |
Class +95/-133 |
6 ft 0 in. (1830 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +35/-49 |
12 ft 9 in. (3885 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +40/-56 |
12 ft 0 in. (3660 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +45/-63 |
11 ft 0 in. (3355 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +50/-70 |
10 ft 0 in. (3050 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +55/-77 |
9 ft 0 in. (2745 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +60/-84 |
8 ft 0 in. (2440 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +70/-98 |
7 ft 0 in. (2135 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
3.0 in. (75 mm) |
FP10 |
Class +85/-119 |
6 ft 0 in. (1830 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +35/-49 |
12 ft 9 in. (3885 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +40/-56 |
11 ft 0 in. (3355 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +45/-63 |
10 ft 0 in. (3050 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +50/-70 |
9 ft 0 in. (2745 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +55/-77 |
8 ft 0 in. (2440 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +65/-91 |
7 ft 0 in. (2135 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.5 in. (65 mm) |
FP10 |
Class +80/-112 |
6 ft 0 in. (1830 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +35/-49 |
12 ft 9 in. (3885 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +40/-56 |
11 ft 0 in. (3355 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +45/-63 |
10 ft 0 in. (3050 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +50/-70 |
9 ft 0 in. (2745 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +55/-77 |
8 ft 0 in. (2440 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +60/-84 |
7 ft 0 in. (2135 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
|
2.0 in. (50 mm) |
FP10 |
Class +75/-105 |
6 ft 0 in. (1830 mm) |
14 ga. [0.0710 in. (1.80 mm)] |
50 ksi (315 MPa) |
Table Notes: Panels rated for Zone H may be used in Zones H and NH.
FP10-Panels through fastened to each steel support with Panel Attachment Screws with Sealing Washers (stainless steel or coated carbon steel 1/4-14 HWH self drilling fasteners with type 3 points for minimum 14 ga. [0.0710 in. (1.8 mm)] steel supports, 1/4-14, 14/4-20, 1/4-28 or 12-24 HWH self drilling fasteners with type 5 points for minimum 3/16 in. (4.75 mm) steel supports or #14-14 HWH self tapping fasteners with type AB, B or BP points through properly sized pilot holes) 8.4 in. (215 mm) on center. See Appendix C.
Tests show 1) that the panels in and of themselves would not create a need for automatic sprinklers and 2) that the panels would be acceptable in a combustible occupancy protected by automatic sprinklers as defined by FM Global Property Loss Prevention Standards.