CFR Roof Panel
Load Span Tables
| CFR-42 ROOF SYSTEM ALLOWABLE UNIFORM LOAD CHART | |||||||
| CFR PANEL THICKNESS |
DESIGN CRITERIA |
ALLOWABLE LOAD (PSF) | |||||
| PANEL SPAN (FT) | |||||||
| 2.5 | 3.0 | 4.0 | 5.0 | 6.0 | 7.0 | ||
| 42" WIDE, 2" THICK 2 FASTENERS/CLIP |
BENDING & SHEAR | 143.8 | 118.0 | 86.2 | 67.7 | 55.7 | 47.3 |
| DEFLECTION (L/240) | 120.3 | 98.3 | 70.6 | 53.8 | 42.4 | 34.3 | |
| CONNECTION | 58.5 | 53.5 | 46.8 | 42.5 | 34.5 | 28.5 | |
| 42" WIDE, 2.5" THICK 2 FASTENERS/CLIP |
BENDING & SHEAR | 165.5 | 135.8 | 99.3 | 77.9 | 64.0 | 54.3 |
| DEFLECTION (L/240) | 147.5 | 121.0 | 87.6 | 67.4 | 53.7 | 43.9 | |
| CONNECTION | 65.0 | 58.5 | 50.3 | 45.1 | 36.6 | 30.4 | |
| 42" WIDE, 3" THICK 2 FASTENERS/CLIP |
BENDING & SHEAR | 184.9 | 152.0 | 111.2 | 87.2 | 71.5 | 60.6 |
| DEFLECTION (L/240) | 171.5 | 141.1 | 102.8 | 79.6 | 63.9 | 52.7 | |
| CONNECTION | 71.3 | 63.5 | 53.6 | 47.6 | 38.7 | 32.2 | |
| 42" WIDE, 4" THICK 2 FASTENERS/CLIP |
BENDING & SHEAR | 196.2 | 161.6 | 118.6 | 93.0 | 76.2 | 64.5 |
| DEFLECTION (L/240) | 210.0 | 173.4 | 127.3 | 99.4 | 80.6 | 67.2 | |
| CONNECTION | 84.0 | 73.4 | 59.9 | 51.8 | 42.4 | 35.7 | |
| 42" WIDE, 5" THICK 3 FASTENERS/CLIP |
BENDING & SHEAR | 223.1 | 184.2 | 135.6 | 106.5 | 87.3 | 73.8 |
| DEFLECTION (L/240) | 235.4 | 194.9 | 143.8 | 112.9 | 92.2 | 77.3 | |
| CONNECTION | 86.5 | 75.5 | 61.8 | 53.4 | 44.4 | 37.9 | |
| 42" WIDE, 6" THICK 3 FASTENERS/CLIP |
BENDING & SHEAR | 247.2 | 204.5 | 151.0 | 118.9 | 97.6 | 82.5 |
| DEFLECTION (L/240) | 247.8 | 205.4 | 152.2 | 120.1 | 98.5 | 82.9 | |
| CONNECTION | 88.8 | 77.6 | 63.5 | 55.0 | 46.3 | 40.0 | |
- Based on CFR-42 panel with 24 ga. exterior face (min Fy = 50 ksi) and 26 ga. interior face (min Fy = 33 ksi).
- Based on attachment at interior supports with CFR panel clip and (2 or 3 as shown above) 1/4"-14 Self-Drilling Tek 3 screws in min. 14 gage steel or (2) 1/4"-14 Self-Drilling Tek 3 screws in min. 12 gage steel. Two fasteners per clip are required at end supports. In lieu of self-drilling screws, self-tapping screws may be used.
- Allowable positive load is the lowest value of panel bending strength, shear strength & deflection limit.
- Allowable suction load is the lowest value of panel bending strength, shear strength, deflection limit and connection strength for each fastener pattern.
- Connection loads may be increased with Fablok. Consult Metl-Span for additional loads.
- The loads based on panel stress and deflection design criteria are derived from ASTM E-72 structural testing. The allowable loads are calculated with a factor of safety of 2.5 and 3.0 for bending and shear stresses, respectively, and deflection limitation of L/240 and with a factor of safety of 2.0 for connection strength.
- The clip fastener capacity was determined from manufacturer fastener pullout data and the allowable loads are calculated with a factor of safety of 3.0.
- The structural capacity of the purlins are not considered and must be examined independently.
- Multiple spans are based on 3 or more spans conditions.
- For allowable snow loads please consult factory.