ROOF PANELS ALLOWABLE POSITIVE AND CONNECTION LOADS (PSF)
CFR PANEL
DIMENSIONS
DESIGN
CRITERIA
SUPPORT SPAN (FEET)
2.53.04.05.06.07.0
42" WIDE, 2" THICKBENDING & SHEAR141.3115.884.866.855.146.9
DEFLECTION (L/240)176.4143.2101.275.758.646.4
CONNECTION39.838.134.831.528.224.2
42" WIDE, 2.5" THICKBENDING & SHEAR163.2133.897.876.863.253.7
DEFLECTION (L/240)204.5167.0119.791.071.657.7
CONNECTION48.746.040.635.229.825.6
42" WIDE, 3" THICKBENDING & SHEAR182.9150.1109.786.070.760.0
DEFLECTION (L/240)229.3188.0136.0104.483.167.8
CONNECTION57.653.946.438.931.527.0
42" WIDE, 4" THICKBENDING & SHEAR195.2160.6117.792.375.664.0
DEFLECTION (L/240)249.6205.8150.7117.294.878.6
CONNECTION75.471.162.553.945.436.8
42" WIDE, 5" THICKBENDING & SHEAR222.1183.2134.6105.786.673.2
DEFLECTION (L/240)283.5234.4172.5135.1110.091.9
CONNECTION75.471.162.553.945.436.8
42" WIDE, 6" THICKBENDING & SHEAR246.1203.4149.8117.896.681.6
DEFLECTION (L/240)313.7259.8192.0151.0123.4103.6
CONNECTION75.471.162.553.945.436.8
  • Based on CFR-42 panel with 24 ga. exterior face (min Fy = 50 ksi) and 26 ga. interior face (min Fy = 33 ksi).
  • Based on attachment with CFR panel clip with (3) 1/4"-14 Self-Drilling Tek 3 screws in min. 14 gage steel or (2) 1/4"-14 Self-Drilling Tek 3 screws in min. 12 gage steel. In lieu of self-drilling screws, self-tapping screws may be used.
  • Allowable positive load is the lowest value of panel bending strength, shear strength & deflection limit.
  • Allowable suction load is the lowest value of panel bending strength, shear strength, deflection limit and connection strength.
  • Connection loads will increase with interior back fastening. Consult Metl-Span for loads and fastening patterns.
  • The loads based on panel stress and deflection design criteria are derived from ASTM E-72 structural testing. The allowable loads are calculated with a factor of safety of 2.5 and 3.0 for bending and shear stresses, respectively, and deflection limitation of L/240.
  • The panel and its connection strength was determined from ASTM E1592 testing, and the allowable loads are calculated with a factor of safety of 2.0.
  • The clip fastener capacity was determined from manufacturer fastener pullout data, and the allowable loads are calculated with a factor of safety of 3.0.
  • The structural capacity of the purlins are not considered and must be examined independently.
  • Reference to multiple spans is based on conditions of 3 or more spans.
  • For SI: 1 foot = 305 mm, 1 psf = 47.9 Pa, 1 inch = 25.4 mm.