2004 MASTER FORMAT™ SECTION 07 42 16
(Previously Section 07413)
METL-SPAN CF ARCHITECTURAL WALL PANEL
WITH METL-VISION INTEGRATED WINDOWS
PART 1 – GENERAL
1.1 SUMMARY
A. Pre-insulated architectural metal panel cladding where indicated on the drawings. Also included are all necessary trims, fasteners, sealants and gaskets as required for a weathertight installation. Panels shall be secured to the structure with concealed clips and fasteners in the sidejoints.
1. Steel faced factory foamed-in-place flat panels with integral reveals with compatible joinery. Panels shall be designed for installation in a horizontal orientation.
2. Integrated Window System for horizontally oriented panels.
3. Extruded aluminum trim related to the walls and its intersection with adjacent materials.
4. Sealants and gaskets between panels, windows and their intersections.
1.2 RELATED SECTIONS
A. Section 07 62 00 (previously 07620) – Sheet Metal Flashing and Trim
B. Section 07 92 00 (previously 07920) – Joint Sealants
C. Section 08 80 00 (previously 08800) – Glass and glazing related to the window system
1.3 REFERENCES
A. AAMA 501.1 – Standard Test Method for Exterior Windows, Curtain Walls and Doors for Water Penetration Using Dynamic Pressure.
B. ASTM A 653 – Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-iron Alloy Coated (Galvannealed) by the Hot-Dip Process.
C. ASTM C 518 – Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus.
D. ASTM E 72 – Standard Test Methods of Conducting Strength Tests of Panels for Building Construction
E. ASTM E 84 – Standard Test Method for Surface Burning Characteristics of Building Materials.
F. ASTM E 119 – Standard Test Methods for Fire Tests of Building Construction and Materials.
G. ASTM E 283 – Standard Method for Determining the Rate of Air Leakage Through Exterior Window, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen.
H. ASTM E 331 – Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Wall by Uniform Static Air Pressure Difference.
I. CAN 4-S101 – Standard Methods of Fire Endurance Tests of Building Construction and Materials.
J. CAN/ULC S102 – Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies.
K. CAN/ULC S127 – Standard Corner Wall Method of Test for Flammability
1.4 PERFORMANCE REQUIREMENTS
A. Structural Tests:
1. The design load/deflection criteria shall be verified from tests per ASTM E 72 “Air Bag Method” using 20 psf (.96 kPa) simulated wind loads. A deflection limit of L/180 shall apply to wall panels.
2. The design load/deflection criteria for the multiple lite window system shall be verified from test per ASTM E 3301-02. At 30 psf positive & negative air pressures, the window assembly deflection shall not exceed L/175. At 45 psf positive & negative air pressures, permanent set of the window assembly shall not exceed 2%.
B. Ther |