Tests & Certifications

Test/Approval Test Method Test Title Results
Fire US ASTM E84 Surface Burning Characteristics of Building Materials Flame spread <25, smoke developed <450
ASTM E119 Fire Tests of Building Construction Materials One hour non-load bearing rating with two layers of Type X Gypsum

Vertical or horizontal installation

FM 4880 Class 1 Fire Rating of Insulated Wall, Ceiling and Roof Panels Product approved

Exterior wall requires FM 4881 approval

NFPA 259 Test Method for Potential Heat of Building Materials Potential heat of foam plastic insulation contained in the assembly tested in accordance with NFPA 285
NFPA 285 Evaluation of Fire Propagation Characteristics of Exterior Non-Load Bearing Wall Assemblies Panel assembly met the requirements of the standard
NFPA 286 Fire Tests for Evaluating Contribution of Wall and Ceiling Finish to Roof Fire Growth Test specimen met the criteria of the IBC Section 803.1.2.1
Fire Canada CAN/ULC S101 Fire Endurance Tests of Building Construction and Materials One hour non-load bearing fire rating with two layers of Type X Gypsum
CAN/ULC S101 Fire Endurance Tests of Building Construction and Materials Meets 15 minute stay-in-place requirements
CAN/ULC S102 Surface Burning Characteristics of Building Materials and Assemblies Meets the National Building Code of Canada requirements
CAN/ULC S134 Fire Test of Exterior Wall Assemblies Complies with the fire-spread and heat-flux limitations required by the National Building Code of Canada
CAN/ULC S138 Fire Growth of Insulated Building Panels in a Full-Scale Room Configuration Met the criteria of the standard
Structural ASTM E72 Strength Tests of Panels for Building Construction See Load Chart
ASTM E1592 Structural Performance of Metal Roof and Siding Systems by Uniform Static Air Pressure Difference See Load Chart
FM 4881 Class 1 Exterior Wall Structural Performance See FM Wall Load Chart
Thermal Performance ASTM C518 Steady-State Thermal Transmission Properties by Means of the Heat-Flow Meter Apparatus K-Factor of 0.126 BTU.in/hr.ft2.°F at 40°F mean core

K-Factor of 0.14 BTU.in/hr.ft2.°F at 75°F mean core

ASTM C1363 Thermal Performance of Building Materials and Envelope Assemblies See Thermal Performance Guide
Air Infiltration ASTM E283 Rate of Air Leakage Through Curtain Walls Under Specified Pressure Differences < 0.01cfm/ft2 at 20 psf

Vertical or horizontal installation

Water Infiltration ASTM E331 Water Penetration of Exterior Walls by Uniform Static Air Pressure Differences No uncontrolled leakage when tested to a static pressure of 20 psf

Vertical or horizontal installation

Special Approval Miami-Dade NOA Product Approval for the City of Miami and Dade County Product has Dade County Notice of Acceptance
State of Florida Product Approval for the State of Florida Product has State of Florida approval