Tests & Certifications

Test/Approval Test Method Test Title Results
Fire US ASTM E84 Surface Burning Characteristics of Building Materials Flame Spread 0, Smoke Developed 0
ASTM E119
CAN/ULC S101
UL 263
Fire Tests of Building Construction Materials Intertek Listings:
-4″ panel: 1 hour vertical or horizontal wall
-6″ panel: 2 hours vertical or horizontal wall
-8″ panel: 3 hours vertical or horizontal wall
-6″ panel: 1 1/2 hour ceiling or floor
ASTM E119
CAN/ULC S101
UL 263
Fire Tests of Building Construction Materials UL Listings:
-4″ panel: 1 hour vertical or horizontal wall
-7″ panel: 2 hours vertical or horizontal wall
-8″ panel: 3 hours vertical or horizontal wall
FM 4880 Class 1 Fire Rating of Insulated Interior Wall and Ceiling Panels Product Approved.

Exterior wall requires FM 4881 approval

ASTM E136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750C Non-Combustible at 750°C or 1382°F
Fire Canada ASTM E 119
CAN/ULC S101
UL 263
Fire Tests of Building Construction and Materials Intertek Listings:
-4″ panel: 1 hour vertical or horizontal wall
-6″ panel: 2 hours vertical or horizontal wall
-8″ panel: 3 hours vertical or horizontal wall
-6″ panel: 1 1/2 hours ceiling or floor
ASTM E119
CAN/ULC S101
UL 263
Fire Tests of Building Construction Materials UL Listings:
-4″ panel: 1 hour vertical or horizontal wall
-7″ panel: 2 hours vertical or horizontal wall
-8″ panel: 3 hours vertical or horizontal wall
CAN/ULC S102 Surface Burning Characteristics of Building Materials and Assemblies Flame Spread 0, Smoke Developed 0
Structural ASTM E72 Strength Tests of Panels for Building Construction See Load Charts
Thermal Performance ASTM C518 Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus K-Factor of 0.275 BTU.in/hr.ft2.°F at 75°F mean core
ASTM C1363 Thermal Performance of Building Materials and Envelope Assemblies See Thermal Performance Guide
Air Infiltration ASTM E283 Rate of Air Leakage Through Curtain Walls Under Specified Pressure Differences 0.04 cfm/ft2 at 12 psf
Water Infiltration ASTM E331 Water Penetration of Exterior Walls by Uniform Static Air Pressure Differences No uncontrolled leakage when tested to a static pressure of 20 psf
Special Approvals State of Florida Product Approval for the State of Florida Product has State of Florida approval